AERINOS BSC-50D

Introduction

AERINOS® BSC-50D is an ultra low power wireless RTU with data logging and alarming capabilities via SMS. The battery powered RTU incorporates a GSM/GPRS modem, a USB serial port, 4 digital inputs, an internal temperature sensor and 1 digital counter. A Lithium Thionyl battery provides autonomous operation for up to 15 years.

The Infinite advantage

BSC-50D utilizes a dual processor architecture in order to combine extreme low power consumption with advanced processing and communication capabilities. A system controller (ultra low power MCU) is in continuous operation scanning the digital inputs for alarm condition detection. A powerful communication processor, switched on and off by the system controller, performs all data processing and controls communications through the internal wireless MODEM. The result is up to 50% power economy in compare with respective units of the competition, while performing the same tasks.

Modes of operation

Modes of operation include power network independent battery operation and USB powered operation for parameter setup.

Alerting & messaging

The digital inputs are scanned in closed loop by the system controller for detecting an alarm condition. The alarm condition (closed or open external contact) is user definable. Alarm limits, sampling period, logging rate, data send rate are user defineable. The unit features a dual set of sampling, logging and data transmission rates. The basic set can be superseded by an alternate set on event. Digital input states, temperature values and counter values can be used as trigger sources for rate changes. Ultra low power standby mode followed by frequent data recording and transmission can be selected to fit the application needs, while maximizing the battery life. SMS announcements include alert messages and periodical status messages for verifying unit availability. The unit supports discrete alerting for several users. Message texts are user definable.

Setup and Remote Configuration

The unit can be programmed locally through the serial port or remotely via SMS by using simple ASCII configuration commands. The command set features commands for configuring input alarm parameters, scaling parameters and alarm limits, timing parameters and defining user groups. BSC-50D can be remotely reconfigured by sending configuration commands via SMS to the unit during the periodical status message processing.

 

Applications

  • Weather conditions & environmental monitoring
  • Water/wastewater level & quality
  • Structural engineering
  • Smart City
  • Oil & Gas
  • Power Grid

Ordering Codes

Code Description
AERINOS BSC-50D-2G Autonomous RTU 2G MODEM
AERINOS BSC-50D-4G Autonomous RTU 4G LTE MODEM

Specifications

Power supply
Supply voltage Internal: 3.6V, 13Ah Lithium Thionyl battery (Saft LSH-20 recommended)
External: 5V (USB power)
Supply current Continuous operation: 40μA, Messaging: average 30mA, 2A peak
Processing units
System controller Ultra low power MCU
Communication processor ARM 9 processor
Inputs/Outputs
Digital inputs 4, dry contact, 0-30VDC
Analog inputs 1, Temperature (Internal sensor), -40°C -125°C
Counters 1, 40Hz max., common with DI4
Communication
Wireless modem Sierra Wireless 2G (HL6528RD), 4G (HL7692 EU, HL7648 US), NBIoT/LTE-M (HL7802)
Antenna Internal or external with SMA connector
Serial interface USB serial, up to 921 kBit/s
Other
Temperature -40°…+65°C, operating
Indications 1, LED, GSM network status, Operation status
Dimensions 124 x 79.5 x 70 mm (with cable gland)
Protection IP66, IP68
Weight 0.3 kg (without battery)
Product Brochures
Document File
AERINOS, BSC-50D Datasheet v2.x  BSC50D Aerinos Datasheet v2.x EN.pdf
Technical Documents
Document File
BSC-50D User Manual v8.x Contact us for the latest document
LSH-20, D-size, Lithium-thionyl battery  LSH20.pdf
WA Manager User Manual v10.x  WA Manager User Manual v10.x
Software
Name File
WA Manager configuration utility v10.67 WA Manager v10.67

Application Documents

  Name   File
Presentation Autonomous RTUs Autonomous RTUs v2
Earth Fault Monitoring for Power Grids Earth Fault Monitoring EFD v5
Presentation IoT for Water Telemetry  IoT for Water Telemetry v2.pdf
Presentation IoT for Structural Engineering & Rail Systems IoT for Structural Eng & Rail Systems v1.pdf