ADS-102, End Node

ADS-102 is a battery powered ProfiSens end node for low voltage, low power sensors. The unit is available for the 433 MHz licence free band. It incorporates two high precision analog inputs, one digital input configurable as pulse counter and a low voltage excitation option for powering measuring transducers. An AA-size Lithium Thionyl battery can provide autonomous operation for over 5 years.

Transducer excitation

The unit provides a 3.6V excitation option for measuring transducers.

Applications

  • Food & Medical Transport
  • Asset Management
  • Agricultural Monitoring
  • Water/wastewater
  • Weather Monitoring

Ordering Codes

Code Description
ADS-102-4 ProfiSens End node, 433 MHz Band, Internal μSplatch™ Antenna (Linx)

Specifications

Power supply
Supply voltage Internal: 3.6V, AA size Lithium Thionyl battery
Consumption
Stand by 18μA max.at 3.6V
Communication 433 MHz Band: Receive: average 31mA, Transmit: average 59mA
Measurement Up to 100mA at 3.6V (according to sensor supply requirements)
Processing unit
System controller Ultra low power ARM 7 MCU
Configuration memory 16 KByte EEPROM
Measurement
Digital inputs 1, dry contact, 0-30VDC
Pulse counter 1, 2KHz, common with DI1
Analog inputs 2, 0-1V (0-2.5V, 0-5V optional), Offset voltage: 50μV max, Input Bias Current 1pA max, A/D conversion 12 bit
Sensor excitation
Output 3.6 VDC, 120mA (with TADIRAN TL-2100 Battery)
Communication
433 MHz Band Input/output impedance 50Ω, Data rate (TX/RX) 4800 bps, Sensitivity -124 dBm, Max output power +10 dBm
Antenna Internal μSplatch™ Antenna (Linx)
Serial interface TTL, up to 115 kBit/s
Other
Temperature -40°…65°C, operating
Indications LED, Operation status
Dimensions 124 x 79.5 x 70 mm (with cable gland)
Protection IP66
Weight 0.3 kg (without battery)
Product Brochures
Document File
AERINOS, ProfiSens IOT Brochure V:3.4 ADU-700 Aerinos Profisens Datasheet v3.4.pdf
Technical Documents
Document File
LSH-20, D-size, Lithium-thionyl battery  LSH20.pdf
WA Manager User Manual v10.x  WA Manager User Manual v10.x
Software
Name File
WA Manager configuration utility v10.67 WA Manager v10.67

Application Documents

  Name   File
Presentation Autonomous RTUs Autonomous RTUs v2
Presentation IoT for Water Telemetry  IoT for Water Telemetry v2.pdf
Presentation IoT for Precision Agriculture  IoT for Precision Agriculture v6.pdf
Presentation IoT for Structural Engineering & Rail Systems IoT for Structural Eng & Rail Systems v1.pdf